Skip to content

Shutter

This chapter describes the bliss.common.shutter.Shutter class, a generic base class for shutter implementation.

To develop a new shutter class, see section: Writing a shutter controller.

Main kinds of shutters in BLISS are:

Screenshot

Shutter API

Here are the common methods usable with shutters.

Basic functions

  • open(): to open the shutter (blocking)
  • close(): to close the shutter (blocking)
  • is_open: true if the shutter is open
  • is_closed: true if the shutter is closed
  • state: return shutter state as a constant
    • one of OPEN, CLOSED, MOVING, FAULT, and few others like UNKNOWN
  • state_string: return the shutter state as a human readable string
    • "Open", "Closed" or "Fault state"

Use the shutter closed and restore it’s original state:

with shutter.closed_context:
    ...  # do something

Use the shutter open and restore it’s original state:

with shutter.open_context:
    ...  # do something

Advanced functions

  • mode property, to specify or tell in which mode the shutter operates

    • MANUAL: the shutter can be opened or closed manually with the .open() and .close() methods
    • EXTERNAL: the shutter is externally controlled - if the external control handler is known to the shutter object, it is used when calling .open() or .close(), otherwise commands will be refused;
    • CONFIGURATION: the shutter is in configuration (tuning) mode, it cannot be opened or closed
  • set_external_control(set_open, set_closed, is_opened): set the shutter in EXTERNAL mode, and create an external control handler using the 3 callback functions passed in parameter (more details below)

  • measure_open_close_time(): put the shutter in MANUAL mode, then do open/close sequence to measure the time it takes
  • opening_time: return known opening time (see .measure_open_close_time())
  • closing_time: return known closing time (see .measure_open_close_time())

External control

External control handler for the shutter can be specified in the configuration, using the external_control key. The corresponding object must derive from a bliss.common.shutter.ShutterSwitch object.

As a convenience, external control handler for a shutter can also be specified using the .set_external_control method. In this case, 3 callback functions have to be passed:

  • function that opens the shutter (e.g. activating BTRIG MUSST output)
  • function that closes the shutter (e.g. setting BTRIG to 0 on MUSST object)
  • function that returns True if the shutter is opened

External control example from MX beamline

This code is part of the MD2S diffractometer controller. fshutter is an IcePAP shutter configured in BLISS. The shutter is set in EXTERNAL mode, it moves when a TTL signal is received on the IcePAP controller. The TTL signal is triggered by the MD2S itself when doing the oscillation (continuous scan). It is possible to generate a TTL pulse by sending commands to the MD2S controller: this is how user can also operate the shutter on demand. The 3 Python lines below show how to use set_external_control to achieve this configuration:

fshutter = config.get("fshutter")

fshutter.set_external_control(
    functools.partial(self._exporter.writeProperty, "FastShutterIsOpen", "true"),
    functools.partial(self._exporter.writeProperty, "FastShutterIsOpen", "false"),
    lambda: self._exporter.readProperty("FastShutterIsOpen") == "true"
    )

IcePap shutter

An IcePAP controller can be used in shutter control mode (using IcePAP LIST MODE). This is done by moving back and forth a stepper motor between two pre-defined positions. The change is triggered by an external signal.

Warning

To enable this mode, an external_control must be configured. It is a switch object that can be:

  • Multiplexer Switch
  • Musst switch
  • Opiom switch
  • Wago switch

Note

external-control keyword is now deprecated in favor of external_control.

Configuration

  • axis_name: name of existing IcePAP axis to move as a shutter
  • closed_position: position of the shutter when it is closed (in user position)
  • opened_position: position of the shutter when it is open (in user position)

Wago switch configuration example:

controller:
   class: icepap
   host: iceid421
   axes:
       - name: the_sheriff
         address: 22
         ...
   shutters:
       - name: fshutter
         axis_name: the_sheriff           # NB: no '$' character.
         external_control: $wago_switch   # external control reference
         closed_position: 0
         opened_position: 1

Opiom Multiplexer switch configuration example:

- class: Switch
  module: multiplexer
  name: fshutter_mux_switch
  mux_controller: $mux_opm1    # opiom mux controller
  mux_name: FSH_MODE           # label of the mux

Musst shutter switch configuration example:

class: Switch
module: musst
name: fshutter_musst_switch
musst: $musst_out
states:
- label: OPEN
  set_cmd: "#BTRIG 1"
  test_cmd: "?BTRIG"
  test_cmd_reply: "1"
- label: CLOSED
  set_cmd: "#BTRIG 0"
  test_cmd: "?BTRIG"
  test_cmd_reply: "0"

Opiom shutter switch configuration example:

class: Switch
module: opiom
name: fshutter_opiom__switch
opiom: $opiom_name
register: IMA
mask: 0x3
shift: 1
states:
   - label: OPEN
     value: 1
   - label: CLOSED
     value: 0
   - label: MUSST
     value: 2
   - label: COUNTER_CARD
     value: 3

Usage

DEMO [1]: fsh
 Out [1]: Shutter (fsh)
          ----------------  ------
          State:            CLOSED
          Mode:             MANUAL
          open position:    20
          closed position:  10
          ----------------  ------

In order to change the values of open or closed positions, the icepap shutter must be put in CONFIGURATION mode:

DEMO [15]: fsh.mode = fsh.CONFIGURATION
DEMO [16]: fsh
 Out [16]: Shutter (fsh)
           ----------------  -------------
           State:            UNKNOWN
           Mode:             CONFIGURATION
           open position:    20
           closed position:  10
           ----------------  -------------

DEMO [20]: fsh.opened_position = 22

DEMO [21]: fsh.closed_position = 12

DEMO [22]: fsh
 Out [22]: Shutter (fsh)
           ----------------  -------------
           State:            UNKNOWN
           Mode:             CONFIGURATION
           open position:    22
           closed position:  12
           ----------------  -------------

And the shutter must be exited from CONFIGURATION mode to be usable:

DEMO [23]: fsh.mode = fsh.EXTERNAL

TangoShutter

TangoShutter class is used to interface Tango Device Servers controlling:

  • frontend
  • safety shutter
  • vaccum remote valves

open() and close() methods are blocking: the TangoShutter object waits the end of the action before returning.

A timeout (60s by default) triggers a RuntimeError in case of failure during the opening or the closing the shutter.

Some commands/attributes (like automatic/manual) are only implemented in the front end device server, set by the _frontend variable.

Usage examples

Example with a safety shutter:

DEMO [1]: bsh1
 Out [1]: Pneumatic Beam Shutter is closed
           - PSS search broken in downstream hutch
           - Experiment interlock
           - RV4 not Open
           - RV6 not Open

Example with a vacuum remote valve:

DEMO [6]: rv9.close()
rv9 was OPEN and is now CLOSED

DEMO [8]: rv9
 Out [8]: Pneumatic is closed

DEMO [10]: rv9.open()
rv9 was CLOSED and is now OPEN

DEMO [11]: rv9
 Out [11]: Pneumatic is open

DEMO [12]: rv9.open()
WARNING 00:13:23 global.controllers.rv9: rv9 already open, command ignored

Configuration

parameters:

  • shutter_type (str, optional) : type of the shutter in : FrontEnd; SafetyShutter; Valve; Generic. If not specified, TangoShutter will try to automatically find the type.
  • uri (str): address of the Tango device

Safety shutter and FrontEnd:

- name: safshut
  class: TangoShutter
  shutter_type: SafetyShutter
  uri: id42/bsh/1

- name: frontend
  class: TangoShutter
  shutter_type: FrontEnd                # shutter_type is optionnal
  uri: acs.esrf.fr:10000/fe/master/id42

Remote valves:

- name: rv0
  class: TangoShutter
  shutter_type: Valve
  uri: id42/v-rv/0

- name: rv1
  class: TangoShutter
  shutter_type: Valve
  uri: id42/v-rv/1

- name: rv2
  class: TangoShutter
  shutter_type: Valve
  uri: id42/v-rv/2

FrontEnd mode

If a TangoShutter is a FrontEnd, a special attribute mode is usable to activate or deactivate the automatic openning mode.

It can be : MANUAL AUTOMATIC or UNKNOWN

Example:

DEMO [3]: fe
 Out [3]: State     : Fault on Front End
          Mode      : No mode is validated!
          Automatic : Automatic opening off
          Type      : UHV

          Module 1 Gate Valve 1: Open
          Module 2 Gate Valve 1: Close

          Fault, pending interlocks are:
           Beam permission loop was opened!
           Cooling fault on module1 fixed absorber
           Interlock from personal safety system

To change the opening mode of a FrontEnd shutter:

DEMO [3]: fe.mode = "MANUAL"
fe mode was AUTOMATIC and is now MANUAL

Example (during a shutdown):

DEMO [7]: fe.mode = "AUTOMATIC"
!!! === RuntimeError: Cannot set AUTOMATIC opening === !!!